AC High  Voltage Vacuum Contactor  12KV One  Pole Phase 400A

AC High  Voltage Vacuum Contactor  12KV One  Pole Phase 400A

Overview CKG3-12/160, CKG3-12/250, CKG3-12/400, CKG3-12/630 AC HIGH VOLTAGE VACUUM CONTACTOR Product Description Product
SHARE

Description

  • Overview
  • Product Description
  • Product Parameters
  • Detailed Photos
Overview
Basic Info.
Model NO. CKG4-400/12-1
Phase 1
Main Circuit Rating Voltage High Voltage
Main Circuit Rating Current 400A
Type Ac Contactors
Standard IEC60947-4-1, EN60947-4-1, UL508
Main 3no power poles
Auxiliary Contact Buil -in 1no, or 1nc, or 1no+1nc
Ambient Temper -25 to +60 centigrade
Class of pollution 3
Intallation Categ 3
Utilization Category AC-3
Theory Electromagnetic Relay
Transport Package Carton
Specification 400A
Origin China
HS Code 8536490090
Production Capacity 500000
Product Description

CKG3-12/160, CKG3-12/250, CKG3-12/400, CKG3-12/630 AC HIGH VOLTAGE VACUUM CONTACTOR

Product Description Product Parameters
Model CKG4-160/12-1 CKG4-250/12-1 CKG4-400/12-1 CKG4-630/12-1
Rated Voltage (KV) (Main Circuit) 12 12 12 12
Rated Current (A) (Main Circuit) 160 250 400 630
Making Capacity (A/100 Operations) (Main Circuit) 1600 2500 4000 6300
Make-Break Capacity (A/25 Operations) 1280 2000 3200 5000
Maximum Break Capacity (A/3 Operations) 3200 3200 4000 6300
Mechanical Life (Operations) 1000000 1000000 1000000 1000000
Power Frequency Withstand Voltage for Main Circuit (KV) 42 42 42 42
Power Frequency Withstand Voltage for Auxiliary Circuit (KV) 2.5 2.5 2.5 2.5
Power Frequency Withstand Voltage for Control Circuit (KV) 2 2 2 2
Rated Operating Frequency (Operations Per Hour) 300 300 300 300
Opening Time (ms) ≤25 ≤25 ≤25 ≤25
Closing Time (ms) ≤40 ≤40 ≤40 ≤40
Clearance Between Open Contacts (mm) 5±0.5 5±0.5 5±0.5 5±0.5
Overtravel (mm) ≥1.2 ≥1.2 ≥1.2 ≥1.2
Detailed Photos