banner

Products

Ckg4 Series High Voltage Vacuum Contactor

Ckg4 Series High Voltage Vacuum Contactor

CKG4 series high voltage vacuum contactor CKG4 series AC high voltage vacuum contactor is widely used in indoor devices
SHARE

Description

Basic Info.
Model NO. CKG4
Phase 3
Main Circuit Rating Voltage High Voltage
Main Circuit Rating Current 630A
Type Ac Contactors
Transport Package Wooden Case
Specification 630A 400A 250A 160A
Trademark RUIHE
Origin Luoyang
Production Capacity 10, 000PCS
Product Description

CKG4 series high voltage vacuum contactor

CKG4 series AC high voltage vacuum contactor is widely used in indoor devices used in power systems with AC 50~60Hz, rated working voltage 12kV and rated current from 160A to 630A. It is used to frequently open and close the load circuit of AC high voltage motors and transformers. This product has a clear structure, which is convenient for commissioning, maintenance and installation.

key word:

CKG4 series high voltage vacuum contactor

Category:

High voltage vacuum contactor

Product details

Product overview

CKG4 series AC high voltage vacuum contactor is widely used in indoor devices used in power systems with AC 50~60Hz, rated working voltage 12kV and rated current from 160A to 630A. It is used to frequently open and close the load circuit of AC high voltage motors and transformers. This product has a clear structure, which is convenient for commissioning, maintenance and installation.

Model and meaning

Technical Parameters Form

Product Dimensional Drawing

Name of parameter

Value

Rated voltage(KV)

12

Rated current(A)

160

250

400

630

Main circuit making capacity (A/100times)

1600

2500

4000

6300

Main circuit break-make ability (A/25times)

1280

2000

3200

5000

Ultimate breaking capacity(A/3times)

3200

4000

4500

6300

Electrical life AC3(Times)

25*104

25*104

25*104

20*104

Electrical life AC4(Times)

10*104

10*104

10*104

10*104

Mechanical life(Times)

10*105

10*105

10*105

10*105

Power-frequency withstand voltage of the main circuit(fracture)(kV)

42

42

42

42

Phase-phase,Phase-ground Power Frequency Withstand Voltage(kV)

42

42

42

42

Power-frequency withstand voltage of the control circuit (kV)

2

2

2

2

Rated operating frequency (Times/h)

300

300

300

300

Terminal Pressure(N)

>100

>100

>150

>150

Clearance between open contacts (mm)

6±0.5

6±0.5

6±0.5

6±0.5

Overtravel(mm)

1.5±0.5

1.5±0.5

1.5±0.5

1.5±0.5

Main Circuit Contact Resistance(µΩ)

≤200

≤200

≤200

≤200



Our Contact