banner

Products

High Voltage Outdoor 12kv Electrical Vacuum Circuit Breaker for Power Systems

High Voltage Outdoor 12kv Electrical Vacuum Circuit Breaker for Power Systems

Overview 1. High Reliability 2. Free of Maintenance during whole Mechanism life 3. High Mechanism Life and Electric Life
SHARE

Description

  • Overview
  • Product Description
  • Design Highlights
  • Product Parameters
  • Main Products
  • Company Profile
  • Certifications
  • Exhibition
  • FAQ
Overview
Basic Info.
Speed High-Speed Circuit Breaker
Arc-extinguishing Medium Vacuum
Installation Fixed
Structure ACB
Poles Number 3
Type Circuit Breaker
Function Conventional Circuit Breaker, Circuit-Breaker Failure Protection, Overcurrent Protection, OVP(Overvoltage Protection)
Certification ISO9001-2000
Rated Current 630A
Closing Time 25~60 Ms
Opening Time 20~55 Ms
Mechanical Life 10000 Times
Transport Package Export Standard
Trademark FUERTE, OEM
Origin China
HS Code 8535210000
Production Capacity 4000sets/Year
Product Description

1. High Reliability 2. Free of Maintenance during whole Mechanism life 3. High Mechanism Life and Electric Life 4. Small in Size, Light Weight, Easy to Install 5. Standard Relay Protection and Fast Reclose Function


Zhejiang Fuerte Electrical Apparatus Co., Ltd. (Formerly Wenzhou Fuerte Electrical Apparatus Co., Ltd. ) was founded in 1985, our company employs 220 staffs, and have down site area 19881m2, covered area 36216m2. As one of the earliest professional manufacturers in China for fuse cutouts, surge arresters, isolating switches, porcelain and polymer insulator and other electrical protection apparatus in China, we've passed ISO certificate (by DEKRA Certification GmbH Stuttgart) and fuse cutouts are tested by CESI, Italy and KEMA, Surge arrester are tested by KEMA also. The scope of business activities includes the production and sale of these electric apparatus. Our company has strong research and development capabilities for customization requirements for our customers. We've designed more than one hundred designs of fuse cutout for customers from different countries; Such as Kenya, South Africa, Morocco, Thailand, Korea, Pakistan, Saudi Arabia, The USA, etc. And same as Surge arrester, isolating switch, porcelain & polymer insulator, and electrical fittings. We believe we can give you most suitable products for your installation request and match the specification of your country.


Our company -- More than 40 years of production experience;

New plant covers an area of 36216m2; employs 220 staffs;

Continuous improvement and perfection of products;

10~38KV voltage level products selection; 100~300A current level products selection; High productivity, large spare parts inventory;

CESI certificate and more laboratory test certification;

Sample order available.

Q: How about the performance of your surge arresters? A: We use reliable material from our supplier and each batch material have qulified certificate. And the assemblied product also 100% tested before package. Q: Can we customize the surge arresters according to our drawing/design? A: Yes, we accept customized order, but the quantity needs to reach at 1000pcs if the mold fee are beared by you. For mold fee beared by us, the quantity need to reach to a large one. Q: What kind of certificate of the surge arrester you have? A: We have KEMA etc.Q: What is MOQ of the surge arrester? A: The MOQ of the surge arrester is 1 piece for sample.Q: What is the warranty for the surge arrester? A: For the all surge arrester, we offer 2 years warranty for free.Q: What is the terms of payment? A: T/T, L/C,western union, trade assurance or cash; 30% for deposit, the balance 70% before shipment.Q: What is the delivery time? A: 3 work days with stock after receiving the payment. No stock, 20 work days after receiving the payment.




Product Description

ZW32 outdoor high-voltage AC vacuum circuit breaker for the rated voltage 12kv, three-phase AC 50HZ outdoor high-voltage power distribution device. It is in line with national standards GB1984-2014 "High Voltage AC Circuit Breaker", JB/T3855-2008 "High Voltage AC Vacuum Circuit Breaker", DL/T 403-2000 "12kV~40.5kV High Pressure Vacuum Circuit Breaker Ordering Technical Requirements" of the relevant provisions. It adopt the unique designed permanent magnet operating mechanism system and high-reliable intelligent controller, suitable for the use of Open/Close of load current, overload current and short circuit current in power distribution device, rural power grid, substation and industrial mining enterprises. Can Auto-reclose 0-3 times.

Design Highlights

Product Parameters

No unit Standard parameter values
1.1 Vacuum Circuit Breaker
1.1.1 Model No ZW32
1.1.2 Switching structure Transformer form Strut external,common box internal
Insulating Material Silicone rnubber over epoxy resin
1.1.3 Dielectric Air
1.1.4 Rated Voltage kV 12
1.1.5 Rated Current A 630
1.1.6 Rated cable charging and breaking current A 25
1.1.7 Rated short-circuit breaking current kA 20,16
1.1.8 Temperature rise test current 1.1Ir
1.1.9 Rated frequency 1 min withstand voltage Relative to/Between kV 42
Intermittent kV 48
1.1.10 Rated lightning impulse withstandvoltage(1.2/50μs)Peak value Relative to/Between kV 75
Intermittent kV 85
1.1.11 Rated short-time withstand current and duration kA/s 20/3
1.1.12 Rated peak withstand current kA 50
1.1.13 Rated short-circuit breaking current kA 20
1.1.14 Rated short-circuit closing cunrent kA 50
1.1.15 Main circuit resistance μΩ Bidder provide
1.1.16 Mechanical stability times ≥10000 No load(5 cycles)
1.1.17 Minimum creepage distance for external insulation mm 372
1.1.18 Rated short-circuit breaking curent breaking times times ≥30times
1.1.19 Closing and opening not synchronized ms ≤2
1.1.20 Contact closing bounce time ms ≤2
1.1.21 Partial discharge(1.1Ur) pC ≤20
1.2 Operating Mechanism
1.2.1 Type Sprung
1.2.2 Operating Method Motorized with manual operation
1.2.3 Motor Voltage V DC24
1.2.4 Instantaneous power of opening and closing W ≤480
1.2.5 Duration of energy storge s ≤15
1.2.6 Energy storage power W ≤240
1.2.7 Closing and opening peak current A ≤20
1.2.8 Auxiliary contact capacity DC24V,10A
1.2.9 DC resistance of telecommunication circuit After 100times operations<192
1.3 Transformer combination mode Includes current transformers.electronic zero sequence voltage transformers,and electromagnetic voltage transformers.
1.4 Current Transformer
1.4.1 Rated current ratio (1)Phase current 600A/5A (2)Zero sequence current 100A/1A
1.4.2 Accuracy Level (1)phase current protection 5P10level,measurement 0.5S(2)Zero sequence current use 100A/1AWhen the input current on the primary side is 1A to the ratedcurrent,it meets the requirements of 1S(ratio difference and angledifference)and the protection accuracy level is 5P10
1.4.3 Implementation method Electromagnetic
1.4.4 Temperature range -20ºC~70ºC
1.5 Electromagnetic voltage transformers(external)
1.5.1 Quantities A.2(for subparagraphs/liaison)
B:1(for branching/dividing)
1.5.2 Rated Voltage Ratio Line Voltage measurement10kV/0.1KVSupply voltage:10kV/0.22kV
1.5.3 Accuracy Level Measuring voltage winding:0.5levelSupply voltage winding:3 levels
1.5.4 Capacity(VA) Measuring voltage winding:≥10VASupply voltage winding long-term capacity≥50VA,Short-time capacity≥300VA/30s